Managing Condensation in New Home Walls and Roofs

Condensation on the inside of a window on a cold winter morning is easy to spot. A bit of that is common and all it really tells you is there’s moisture in the air inside, so run the exhaust fans and air the rooms out. The water you should worry about more is the stuff you can’t see, collecting inside walls and up in the roof space where the timber, plasterboard and insulation are. Leave that long enough and you can end up with mould and damaged building materials.

Newer houses are sealed up tighter and insulated better than old ones. Great for comfort and power bills. But it does change the way moisture moves around the house, and the National Construction Code now has condensation rules for houses. If you’re planning a new build or an extension, it’s worth getting your head around the main ideas.

Where the water comes from

The air inside your house is full of water vapour from cooking, showers, washing and just people breathing. When warm air hits something cold, the vapour turns back into water. On a window you see droplets. Inside a wall or a roof it can happen where nobody’s looking, on the back of the cladding or the underside of the roof.

In a tightly sealed house that moisture has fewer ways to get out. And insulation keeps the outside layers of a wall colder in winter. Put those together and your walls and roof need a planned way for the moisture to escape. A good designer thinks about the whole outer shell of the house together, and doesn’t just pick products one at a time.

What the code covers

The Australian Building Codes Board puts out the National Construction Code. For houses, the condensation rules are in Part 10.8 of the ABCB Housing Provisions on condensation management, and they deal with wall membranes, exhaust fans and roof space ventilation. A lot of it depends on which climate zone you’re building in.

NCC 2022 tightened up several of these rules. The ABCB’s summary of the NCC 2022 condensation changes notes that many exhaust systems now have to discharge outside and can’t just dump into the roof space, and that roof spaces in colder climate zones need ventilation openings. NCC 2025 started applying in Victoria and the ACT from 1 May 2026 and has more condensation measures again. Your designer or building surveyor will tell you which version applies to your job.

Wall wrap

Most framed walls have a pliable building membrane behind the cladding, often called wall wrap. It’s meant to shed liquid water but still let water vapour out of the wall. How easily the vapour gets through is called vapour permeance, and the Housing Provisions set minimum values for membranes on the outer side of the insulation.

In climate zones 4 and 5 the minimum is 0.143 µg/N.s. In zones 6, 7 and 8 it goes up to 1.14 µg/N.s. Class 3 and Class 4 membranes under AS 4200.1 meet the lower figure, but only Class 4 meets the higher one for the colder zones. Your designer or surveyor can confirm which class your site needs.

If wall wrap is used, it has to comply with AS 4200.1, be installed to AS 4200.2 and sit on the outer side of the main insulation layer. If there’s no wrap, the code calls for a drained cavity to keep the water control layer apart from materials water can damage. Single skin masonry and concrete get treated differently.

Fans, dryers and the roof space

Most of the moisture in a house comes out of the bathroom, kitchen and laundry. The Housing Provisions set minimum exhaust flow rates of 25 litres a second for a bathroom or toilet and 40 litres a second for kitchens and laundries. Those exhausts have to go out to outdoor air, either directly or through a shaft or duct. Venting clothes dryers have to go outside the same way. A fan that just blows damp air into the roof hasn’t fixed anything, it’s only moved the problem somewhere you can’t see it.

Rooms with exhausts that aren’t otherwise ventilated also need a way for replacement air to come in, and the code allows openings with a free area of 14,000 square millimetres to the next room. The ABCB summary also mentions a rule for bathrooms that don’t have enough access to outdoor air. Their exhaust has to come on with the light and keep running for 10 minutes after the light’s switched off. Undercutting the bathroom door is one simple way to let replacement air in. Small stuff, but it makes a big difference to how dry the room stays.

Up in the roof, climate zones 6, 7 and 8 need the roof space ventilated. The space has to be at least 20 mm high. How big the openings are depends on the roof pitch, and it’s set per metre of the longest roof dimension. For a roof pitched at 15 degrees or more, the table asks for 7,000 square millimetres per metre at the eaves and 5,000 square millimetres per metre at high level. A cathedral ceiling at that pitch needs another 18,000 square millimetres per metre at the eaves. High level openings sit at the ridge or no more than 900 mm below it.

Some roofs don’t need it at all. Concrete roofs, structural insulated panel roofs and roofs in the BAL FZ bushfire flame zone are exempt.

Inside and out

The frame is just one part of it. Inside, glass is usually where you first notice moisture. Some owners look at coatings for windows and shower screens, and our article on nano glass protection explains how those products work. Floor coverings come into it as well, because damp rooms are hard on natural fibres like the ones in our guide to cleaning and maintaining wool carpets.

Outside, don’t let garden beds and soil build up against the walls. Our guide to mulching garden beds is a good reminder to keep mulch back from weep holes and cladding. Timber and composite outdoor surfaces each deal with moisture in their own way too, so if a new deck’s going to sit right up against the house, read through the pros and cons of composite decking before you choose.